Figure 1-2. Location of Major Components
Figure 2-1. Operator Control Panel

Test Set, Electrical (0-33Kw Load Bank) Model 1057 Page Navigation
  1    2    3  4  5    6    7    8    9  
TM5-6625-2694-13&P
1-8.
Equipment Data.
Manufacturer . . . . . . . . . . . . . . . . T e c h n i c a l
Services
Laboratory,
Inc.
D i m e n s i o n s . . . .... . . . . . . . .. . . . . . . 2 2 . 5 " W , 2 4 " H , 3 6 " L
W e i g h t . . . . . . . . ...... . . .. . . . . . .. . . . . . . 2 2 5
lbs.
Model No . . . . . . . . . . . . . . . . . . . . .Model 1057
Operating Modes . . . . . . . . . . . . . . . . 120/208 4W
240/416 4W
120/240  3W
(Note  1)
120/2w
(Note 2)
240/2W
(Note 3)
Operating Temperatures . . . . . . . . . .
. . . . . 0 - 50 Degrees Centigrade
NOTES :
(1)  120/240  Neutral
not  used  -  high  power.
(2)  Phase  shorting
link  -  neutral  return.
(3)  Phase  shorting
link  -  neutral  return.
Section
III.
TECHNICAL
PRINCIPLES
OF
OPERATION
1-9.
The  Model  1057  Test  Set
utilizes  switchable
fixed  air-cooled
resistors  to  present  various
loads  from  O-33  KW  to  the  generator.
The  resistor  loads  are  arranged  in  groups  of  three,  thereby  allowing
the  Test  Set
to  present  balanced  loads  to  three
phase  generators.  A
shorting  link  connects  the  three
groups
of  resistors  in  parallel  for
loading
single  phase  generators.
A  voltage  sensing  module
monitors
the  input,  automatically  determining  whether
the  control  circuits  are
for
configured
HI
or
This
LO  input  voltage.
module
works  in
conjunction  with  the  Voltage  Input  Selector
(P1) to prevent damage to
the
Test  Set
should
improper
voltage  be  applied  to  the
input
terminals.
1-4