TM 5-6350-275-24&P
3-131. STARPIN KEYPAD OPERATION (CON'T)
Press F2 (SLF) and F4 (SGL) simultaneously to start the display sequence. The keypad displays each sensor as it is
listed in the Stargate database. The display shows the sensor name and the current condition of the sensor and the
tamper alarm. For example:
WLK SLF ZNE SGL
PIR 1 OK OK
Select F3 (HALT) on the sensor point to be tested. The display freezes on this sensor. To move up or down to other
sensors, use F1 (UP) or F3 (DOWN). When the display shows the correct sensor, select F4 (OPER).
WLK SLF ZNE SGL
PIR 1 ST OK
If the test is completed correctly, the display changes to:
WLK SLF ZNE SGL
SGL SELF TEST OK
This indicates successful completion of a self test. If the test fails, the display will indicate "Test Failure".
After the test, the readout will return to the third level menu. If no additional requests are made, the readout will return to
the login screen.
Step 8. Self Test Zone
The keypad single test mode provides a test of any zone or 24 hour sensor by controlling the test circuit of the individual
sensors. Only sensors with this feature can be tested in this way. The single test can be operated only from an accessed
zone.
To single test a sensor, at the first menu enter you PIC number followed by GO. The following menu appears:
SEC EXT CMD DIS
Select F4 (DIS). The LCD shows the second level soft key options: ALM 24H MTC HST.
Enter F3 (MTC) for
maintenance mode to provide the third level menu:
TST SNT CLR
Select F1 (TST) for the test functions. The keypad displays the fourth level menu.
WLK SLF ZNE SGL
Press F2 (SLF) and F3 (ZNE) simultaneously to start the sequence. The keypad displays:
(PRESS OPER)
3-242