CHAPTER 3. OPERATOR/CREW MAINTENANCE INSTRUCTIONS
Figure 3-1. Fuse Location

Test Set, Electrical (Load Bank,) 0-30 Kw, Ac; Portable Skid-Mounted Page Navigation
  15    16    17    18    19  20  21    22    23    24    25  
img
. . . . .
TM 6625-2691-13&P
3-6. Troubleshooting
test set or its components. You should perform the
tests/inspections and corrective actions in the order
Table 3-2 lists the common malfunctions that you
listed.
may find during the operation or maintenance of the
Table 3-2. Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
NOTE
Before you use this table, be sure you have performed all normal operational checks. If you have a malfunction which is not listed
in this table, notify the next higher level of maintenance.
1. TEST SET FAILS TO START
Step 1. Inspect for a defective fuse by removing the three holder caps (fig. 3-l). Turn the caps counterclockwise, and pull the fuses out.
Inspect the fuses for burns, cracks or breaks.
Replace the fuse with a fuse of the same rating and size. Replace fuse holder cap by screwing full clockwise
until snug. Do not overtighten.