TM 5-6350-275-24&P
Table 3-9. Sensors DS Maintenance Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
6. RADIO FREQUENCY MOTION SENSOR FAILURE (continued)
Step 7. Place multimeter negative lead on TB1 pin 1 and positive lead on pin 2. The multimeter should read
from +11 to +15 v.
If multimeter reading is correct, go to step 8.
If multimeter does not read between +11 and +15 v, replace input power source.
Step 8. Place multimeter negative lead on TB1 pin 9 and positive lead on Test Point TP5. The multimeter
should read between +3.5 and +5.5 v.
If multimeter reading is correct, replace RFMS Receiver PWA (Para. 3-124).
If multimeter reading is not correct, replace RFMS Transmitter PWA (Para. 3-124).
3-55