REMOVAL AND INSTALLATION PROCEDURES
REFERENCES

Maintenance Manual For Control Unit, Alarm Set C-9412/Fss-9(V) -12 Page Navigation
  39    40    41    42    43  44  45    46    47    48    49  
TM 5-6350-264-14&P-12
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
TO 31S9-2FSS9-1-12
tor lights should flash and the audi-
(4) Turn mode switch to ACCESS.
ble signal device should sound.
Monitor Cabinet should indicate
an access condition.
(8) Move reset switch on Status Moni-
tor Module to ACK. AC POWER
(5)
Remove ac power fuse F1 from CU
indicator lights should change from
power supply. AC POWER indica-
flashing to on steady and the audi-
tor lights on Monitor Cabinet
ble signal device should be silenced.
should change from on-steady to
flashing, and the audible signal
NOTE
device should sound.
Code plugs cannot be tested. If
(6) Move reset switch on Status Moni-
you suspect a bad code plug, install
tor Module to ACK. Indicator lights
two new plugs with matching
should go out and audible signal
serial numbers. Bad or mismatched
device should be silenced.
code plugs will most probably re-
sult in continuously changing status
(7) Reinstall ac power fuse F1 in CU
indications at the Monitor Cabinet.
power supply. AC POWER indica-
5-33/( 5-34 blank)