• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
Table 5-1. Troubleshooting Procedures - Continued
Table 5-1. Troubleshooting Procedures - Continued

Maintenance Manual For Control Unit, Alarm Set C-9412/Fss-9(V) -11 Page Navigation
  23    24    25    26    27  28  29    30    31    32    33  
img
TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
rack. Remove screws that se-
cure Status Monitor Module to
rack and remove module
through front of rack.
f.
Remove jumper from terminals 3
and 4 of Status Monitor Module
terminal board. Replace Status
Monitor Module in swingout
rack and secure with screws. Se-
cure swingout rack. Turn on
switch S1 on power supply.
g.
If AC POWER lights are not lit,
Status Monitor Module is de-
fective.
h.
To remove Status Monitor Module,
unlock and open Monitor Cabi-
net and turn off switch S1 on
power supply. Release swingout
rack. Remove screws that se-
cure status monitor module to
rack and remove module
through front of rack. Install
new Status Monitor Module in
swingout rack and secure with
screws. Secure swingout rack.
Turn on switch S1 on power
supply.
5.
In SECURE mode
Defective Status Monitor
a.
Remove Status Monitor Module
Status Monitor
Module.
from one-zone Monitor Cabinet.
Module does not dis-
To remove Status Monitor Mod-
play a tamper condi-
ule, unlock and open Monitor
tion.
Cabinet and turnoff switch S1
on power supply. Release
swingout rack. Remove screws
that secure Status Monitor Mod-
ule to rack and remove module
through front of rack.
b.
Connect jumper between terminals
1-I, 1-L, and 4 of associated
Monitor Cabinet input ter-
minal strip. Replace Status
5-8


Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved.