Table 5-1. Troubleshooting Procedures - Continued
Table 5-1. Troubleshooting Procedures - Continued

Maintenance Manual For Control Unit, Alarm Set C-9412/Fss-9(V) -11 Page Navigation
  22    23    24    25    26  27  28    29    30    31    32  
img
TM 5-6350-264-14&P-11
NAVELEX EE 181-AA-OMI-120/E121 C-7359-60-1
T.O. 31S9-2FSS9-1-11
Table 5-1. Troubleshooting Procedures - Continued
Trouble
Probable cause
Corrective Action
h.
To remove Status Monitor Module,
unlock and open Monitor Cab-
inet and turn off switch S1 on
power supply. Release swingout
rack. Remove screws that se-
cure Status Monitor Module to
rack and remove module
through front of rack.
i.
Install new Status Monitor Module
in swingout rack and secure
with screws. Secure swingout
rack. Turn on switch S1 on
power supply.
4.
Status Monitor
Defective Status Monitor
a.
Remove Status Monitor Module
Module does not
Module
from one-zone Monitor Cabinet.
correspond to ac
To remove Status Monitor
power condition at
Module, unlock and open Mon-
Control Unit.
itor Cabinet and turn off switch
S1 on power supply. Release
swingout rack. Remove screws
that secure Status Monitor Mod-
ule to rack and remove module
through front of rack.
b.
Connect jumper between terminals
3 and 4 of applicable Status
Monitor Module terminal board.
Replace Status Monitor Module
in swingout rack and secure
with screws. Secure swingout
rack. Turn on switch S1 on
power supply.
c.
Actuate ACKNOWLEDGE then
RESET switch on Status Mon-
itor Module.
d.
If AC POWER lights are lit, Status
Monitor Module is defective.
e.
To remove Status Monitor Module,
unlock and open Monitor Cabi-
net and turn off switch S1 on
power supply. Release swingout
5-7