Page Title: Table 5-1. Direct Support Troubleshooting (cont)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM5-6625-2694-13&P
Table
5-1.
Direct
Support
Troubleshooting
(cont'd.)
MALFUNCTION
TEST
OR
INSPECTION
CORRECTIVE
ACTION
ONE
OR
TWO
FAN
MOTORS
DO
NOT
RUN.
Step
1.
does
not
run
and
associated
Check
Fan
Motor(s)
that
components.
Fan M o t o r
at
voltage
a.
Check
leads
to
across
Terminal
15
(+)
to
terminal
terminal
strip.
16
(-)
should
be
24
VDC.
b.
Refer
to
5-7
and  replace  Fan  Motor(s)
if
24
VDC
is
present  and
Fan
Motor(s)  does  not  run.
with
Rectifier
Bridge(s)
associated
Fan
Step
2.
Check
Motor(s)
that  does  not  run.
-
terminal
Measure
voltage
a.
across  +  terminal
and
be
24
VDC.
Rectifier
Bridge;
should
Measure
on
voltage
across
AC
terminals;
should
be
24
VAC.
Refer
to
b.
and
replace
Rectifier(s)
if  24  VAC  is  present  across  AC
terminals  and
0
VDC
is
present  across  +  terminal  and  -
terminal.
with
Fan
Step
3.
24
V.
Transformer(s)
Check
associated
Motor(s).
terminal
a.
Measure
voltage
output
5
and
terminal
6
of
associated
Transformer(s);  should
be
24
VAC.
Measure
terminal
b.
input
1
and
voltage
across
terminal
4
of
With
associated
input
Selector
Voltage
Plug
in
LO
position
With
Voltage
Selector
measurement  should  be  120  VAC
.
position,  m
easurement  should  be
Plug  in  HI  input
240
VAC.
to p a r a g r a p h 5 - 1 5  a n d
c.
Refer
replace
Transformer(s)
if
input
voltage
is
correct
and
output
is
NOT
24
VAC.
5-4 C h a n g e
1