TM 5-6350-275-24&P
Table 3-9. Sensors DS Maintenance Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 1. Ensure door, window, vent, or type of entry being protected is properly closed or fastened and all
mounting hardware is present and tightened down. Check gap between magnet and sensor unit to
ensure it is within specified distance according to model number of BMS sensor.
If sensor is still in alarm, go to step 2.
Step 2. Remove the sensor input cable from the Leda Flex Termination PWA or Stargate PWA termination
board. Go to sensor output cable assembly interface terminal strip and remove cover. Using a multimeter,
place function switch to ohms. Place black lead from multimeter on common lead (6). Place red lead from
multimeter on closed loop lead (4). The multimeter should read continuity with door closed.
If meter does not show continuity, replace BMS (Para. 3-111, 3-112, or 3-113).
If meter shows continuity, go to step 3.
Step 3. Open portal to unbalance the BMS. The meter should change from a continuity indication to an open
circuit indication.
If indication is correct, the BMS is good, or if the BMS has a tamper switch, go to step 4.
Step 4. Place black lead from multimeter on Supervised common lead (7). Place red lead from multimeter on
Tamper lead (8). The multimeter should indicate continuity.
If multimeter does not indicate continuity, replace the BMS (Para. 3-111, 3-112, or 3-113).
If multimeter indicates continuity, the BMS is good. Go to troubleshooting steps for the RADC (Table 3-
3).