Table 5-1. Troubleshooting Procedures - Continued
Section IV. REMOVAL AND REPLACEMENT OF MAJOR COMPONENTS AND ASSEMBLIES

Maintenance Manual For Control Unit, Alarm Set C-9412/Fss-9(V) -5 Page Navigation
  10    11    12    13    14  15  16    17    18    19    20  
img
TM 5-6350-264-14&P-5
NAVELEX EE 181-AA-OMI-060/E121 SA-1955
T.O. 31S9-2FSS9-1-5
Table 5-1. Troubleshooting Procedures Continued
Trouble
Probable cause
Corrective action
2. (cont)
c. (cont)
h. If the meter indicates more than 50
ohms, reposition the bias magnet
until the meter does indicate less
than 50 ohms.
i. Open the door or window 1 1/4 inch
(3.175 cm). The meter should
indicate over 100,000 ohms.
j. Repeat these steps until the meter
indicates less than 50 ohms with
the door or window open 1/2
inch(1.27  cm)  or  less,  and
indicates over100,000 ohms when
the door or window is opened more
than1-1/4 inch (3.175 cm).